  • SMOKE AND COMBINATION - Ruskin
    The operational test shall be conducted under non-fire HVAC airflow conditions as well as static flow conditions All indicating devices shall be verified to work and report to the intended location The dynamic combination fire smoke damper shall also meet the testing requirements contained in Chapter 6 of NFPA 105
  • Code Required Testing of Fire, Smoke and Combination Dampers
    The operation must be under the airflow conditions that the system will encounter Fusible links must comply with NFPA 90A and UL33 10 Documentation must be maintained and any deficiencies reported and corrective action noted It also states that "repairs shall begin without delay" and following repair shall be operational tested again
  • IOM-FSDIMP - Nailor
    All requirements of testing for actuated smoke and fire smoke dampers are to be conducted under normal HVAC airflow conditions
  • Fire and Smoke Damper ITM - NFPA
    What are the inspection, testing, and maintenance requirements for fire and smoke dampers?
  • MAINTENANCE AND TESTING OF FIRE SMOKE DAMPERS
    Where a fusible link is installed on a combination fire smoke damper, the link must be removed for testing the damper for full closure simulating a fire condition per the requirements and frequencies of NFPA 80
  • Fire, Smoke, and Combination Fire Smoke Dampers - FCIA
    “The operational test shall be conducted under normal HVAC airflow conditions as well as static flow conditions The damper shall fully close seal under both test conditions ”
  • Interstate Life Safety - Nfpa 80, Damper Inspections, Nfpa 101
    19 3 2 2 The operational test shall be conducted under non fire HVAC airflow conditions as well as static flow conditions 19 3 2 3 The operational test shall verify that there are no obstructions to the operation of the dynamic combination fire smoke damper
  • Fire, Smoke, and Combination Fire Smoke Dampers
    Damper Ratings Operational Airflow Rating (400 fpm safety) 2000 fpm 3000 fpm 4000 fpm